50NG
Sensitive residual or phase overcurrent element pickup (0.25-50,000 primary
amperes)
50P
Phase overcurrent element pickup (0.25-50,000 primary amperes)
50H
Phase overcurrent element high pickup (0.25-50,000 primary amperes)
51NP
Residual time-overcurrent pickup (0.25-50,000 primary amperes)
51NTD
Residual time-overcurrent time dial (0.5-15)
51NC
Residual time-overcurrent curve index. Choices are as follows:
Use 1 to select a moderately inverse curve
Use 2 to select an inverse curve
Use 3 to select a very inverse curve
Use 4 to select an extremely inverse curve
51NTC
Do you want residual time-overcurrent torque control? (Y or N)
67NP
Residual instantaneous overcurrent pickup (0.25-50,000 primary amperes)
67NTC
Do you want residual instantaneous overcurrent torque control? (Y or N)
52BT
52B time delay (0.5 to 10,000 cycles)
REJOE
Should permissive tripping be allowed when the remote end just opens? (P,G, or N)
LOPE
Loss-of-potential detection function (Y, N, 1, 2, 3, 4)
TIME1
Timeout for PORT 1 (0-30 minutes)
TIME2
Timeout for PORT 2 (0-30 minutes)
AUTO
Autoport (PORT 1, 2, or 3)
RINGS
The number of rings after which the modem answers (1-30 rings)
Refer to the functional description and be sure the settings you choose result in relay
performance appropriate to your application.
The AUTO setting selects PORT 1, PORT 2, or both serial ports for automatically transmit-
ted messages. If PORT 2 of the relay is connected to an SEL-DTA or SEL-PRTU, the
AUTO setting must direct automatic messages to that port. The following table shows the
effect of each possible setting:
Auto
Automatic Message
Setting
Destination Port
1
1
2
2
3
1 and 2
Event summaries and self test warning and failure reports are automatically transmitted from
port(s) designated automatic regardless of access level, if the designated port is not timed out.
Enter zero as the timeout setting of the appropriate port if automatic transmissions will be
monitored by a dedicated channel, printed on a dedicated printer, or if that port is connected
to an SEL-DTA, SEL-RD, or SEL-PRTU.
Date Code 920508
Communications
SEL-221F, -1 Instruction Manual
3-23
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...