4.
Adjust the voltages and currents of the test set to the values shown in
Table 7.4. Do not turn on the currents at this point.
5.
Turn on the voltage sources VA, VB, and VC.
6.
Apply current to the relay and ramp the current source magnitudes together
until the monitored output contact closes, indicating pickup. Record the pickup
current threshold and compare to the calculated threshold.
To calculate the phase distance element reach for a three-phase fault you need
only consider a single phase. For example, if the A-phase voltage magnitude is
34.58 V
1-n
and the current magnitude for the boundary characteristic is 5.33 A,
calculate the phase distance element reach as follows:
Zone 1 reach secondary,
secondary along the MTA
In primary ohms,
Zone 1 reach primary along the MTA,
primary
Where PTR = 2000 and CTR = 200.
7.
Obtain two other convenient test points. Consider a square inscribed in a mho
circle with one diagonal being the diameter along the MTA. The two corners
of that square on the other diagonal are reached by increasing the current by a
factor of 1.414 at angles of ±45° away from the angle obtained using the
BASIC program.
For the three-phase example, the required voltages do not change. The current
magnitudes are 5.33 A (1.414) = 7.54 A at the angles listed as follows:
Table 7.5: Zone 1 Three-Phase Fault Test Quantities at MTA ±45°
Angle IA
Angle IB
Angle IC
MTA +45°
-125.1°
114.9°
-5 .1°
MTA - 45º
-35.1°
-155.1°
84.9°
8.
Test the relay at the two additional current phase angle settings (MTA +45°
and MTA -45°). Record the results.
Date Code 921110
Maintenance & Testing
SEL-221F, -1 Instruction Manual
7-21
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...