The CLOSE command asserts the CLOSE output relay. You can also accomplish this by
asserting the DIRECT CLOSE input as long as the 52A input or TRIP outputs are not
asserted. The CLOSE output relay then remains closed until the 52A input is asserted
(indicating that the circuit breaker is closed) or until the reclose reset timer (79RS) expires.
To close the circuit breaker with this command, type
CLOSE <ENTER>.
The prompting
message "Close BREAKER (Y/N)?" is displayed.
Y <ENTER>
yields a second prompt-
ing string: "Are you sure (Y/N)?" Type
Y <ENTER>
to assert the CLOSE output relay,
as long as the TRIP output and 52A input are not asserted. The relay transmits the message
"Breaker CLOSED" once the breaker closes, or if it is already closed (as determined by the
state of the 52A input). Typing
N <ENTER>
after either of the above prompts aborts the
closing operation with the message "Aborted."
Install jumper JMP104 to enable the CLOSE command.
LOGIC n
The LOGIC command programs the masks which control outputs and event report triggering.
The parameter n specifies a mask to program.
MTU -
Mask for trip unconditional
MPT -
Mask for trip with permissive-trip asserted
MTB -
Mask for trip with block-trip deasserted
MTO -
Mask for trip with breaker open
MA1 -
Mask for A1 relay control
MA2 -
Mask for A2 relay control
MA3 -
Mask for A3 relay control
MA4 -
Mask for A4 relay control
M R I -
Mask for reclose initiate
MRC -
Mask for reclose cancel
The logic programming procedure requires you to enter changes to the mask or press
<ENTER>
to indicate no change. Each mask listed above is split into sections which
correspond to the three rows of the Relay Word as follows:
Relay Word 1:
Z1P
Z1G
Z2PT
Z2GT
Z3
Z3T
3P21
32Q
Relay Word 2:
67N
51NP
51NT
50NG
50P
50H
IN1
REJ0
Relay Word 3:
L0P
52BT
27S
27P
59S
59P
SSC
VSC
3-18
Communications
SEL-221F, -1 Instruction Manual
Date Code 940412
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...