The following is the first four cycles (quarter-cycles 1 - 16) of Example Event Report 2,
showing prefault and fault inception conditions.
The event report uses a sequence of event format which allows performance analysis of the
system by quarter-cycles. Through this analysis, you can observe the prefault voltage and
current conditions prior to the fault, determine whether or not the breaker was closed by the
52A Inputs column and line current magnitudes, and learn when the protective elements
assert. The following outline lists observed incidents shown in Example Event Report 2 by
quarter-cycle.
Quarter
Cycle Event Report Shows:
1 - 14
Prefault conditions:
No protective relay elements are picked up
5 in 52A Inputs column verifies breaker closure (as does load current flow)
15
Fault Inception:
G in 50P column shows phase current reached 50G element pickup threshold
P in 50NG column shows phase current reached 50N element pickup threshold
16
P in 51N column shows that the ground time-overcurrent element picked up
The ground time-overcurrent element picked up in row 16 because the residual current was
above the 51NP setting and the 32Q directional element indicated that the fault was in the
forward direction.
Date Code 920423
Event Reporting
SEL-221F, -1 Instruction Manual
4-13
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...