5.
Set a second contact to close upon assertion of the SSC bit. Connect that
contact to stop the external timer.
6.
Connect a voltage source to the synch-check voltage input. Apply voltage
above the 59VHI setting. When the 59S bit asserts, the external timer should
start. When the sync check voltage conditions have been valid for 25T time,
the SSC bit should assert, stopping the external timer. Verify that the timer
reading is equal to the 25T timer setting.
Figure 7.12: Voltage Connections When SYNCP = A
INPUT CIRCUITS TEST
Purpose:
Verify that logic inputs assert when control voltage is applied across the
respective terminal pair.
Method: 1.
Set target LEDs to display the contact inputs by typing
TAR 5 <ENTER>.
The front panel LEDs should now follow the contact inputs.
2.
Apply control voltage to each input and make sure the corresponding target
LED turns on. Energizing the PT, IN1, and ET inputs should trigger an event
report. Table 7.18 lists the contact inputs and terminal numbers.
7-40
Maintenance & Testing
SEL-221F, -1 Instruction Manual
Date Code 920508
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...