For the relay at Breaker 3:
- Setting Limit Check
The primary limit check allows Zone 2 percent reach settings of 0 - 3200% with the require-
ment that the Zone 2 reach be equal to or greater than the Zone 1 reach. The secondary
check allows secondary reach settings of 0.125 - 64 ohms secondary along the MTA.
Calculations:
PTR = 2000:1
PTR/CTR = 10
CTR = 200:1
The Z2% setting of 120 for this example lies within the secondary setting limits of the relay.
- Relay Word Bits and Other Settings Affected
Zone 2 must be less than Zone 3. The Z2PT and Z2GT bits in the Relay Word depend on
the Z2% setting.
Zone 3 Reach Setting (Z3%)
The Zone 3 elements time delayed outputs can serve as remote backup for faults beyond the
far bus.
For the relay at Breaker 3:
- Setting Limit Check
The primary limit check allows Zone 3 percent reach settings of 0 - 3200%, with the require-
ment that Zone 3 reach exceed Zone 2 reach. The secondary check allows secondary reach
settings of 0.125 - 64 ohms secondary along the MTA.
Calculations:
PTR = 2000:1
PTR/CTR = 10
CTR = 200:1
Date Code 921110
Applications
5-15
SEL-221F, -1 Instruction Manual
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...