For our Zone 1 BC phase-phase example, the required voltages remain
unchanged. The current magnitudes are (4.61)(1.414) = 6.52 amperes at the
angles listed as follows:
Table 7.7: Zone 1 Phase-Phase Test Quantities at MTA ±45°
Angle IB
Angle IC
MTA +45°
144.9°
-35.1°
MTA -45°
-125.1°
54.9°
8.
Test the relay at the two additional current phase angle settings (MTA +45°,
MTA -45°). Record the results.
F. Phase-Ground Mho Element Tests
Purpose:
Determine the pickup of the ground distance element at three points on the mho
characteristic: MTA, MTA +45° and MTA -45°.
Method: 1.
Use the LOGIC command to program a single output relay (A1 - A4) to follow
the appropriate instantaneous ground distance element. Select a ground element
from the Relay Word as indicated below:
Z1G
=
Zone 1 Instantaneous Ground Distance Element
Z2GT =
Zone 2 Time Delayed Ground Distance Element
Z3
=
Zone 3 Instantaneous Phase and Ground Distance Element
Please note the Z2GT element includes any delay set by the Z2DG timer.
The following example outlines the test procedure for the Zone 1 ground
distance element.
2.
Connect the sources of voltage and current to the relay rear panel terminals (see
Figure 7.10).
These steps connect a single current source to the relay for a A-phase-ground
fault test.
a .
Connect A current source dotted output to dotted relay IA input
(Terminal 29).
b.
Connect A current source return to relay IA return (Terminal 30).
Date Code 920508
Maintenance & Testing
SEL-221F, -1 Instruction Manual
7-25
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...