Enables from Setting Procedure
Select torque control for 51N
51NTC
Select torque control of 67N
67NTC
Remote-End-Open Perm. Trip Enable REJOE
Loss-of-potential enable
LOPE
Intermediate Logic
The logic equations developed below represent combinations of the relay elements and other
conditions. In the following equations,
"
*
"
indicates a logical
"
and,
"
while
"
+
"
indicates a
logical
"
or.
"
Loss-of-Potential (LOP) Logic
Set
LOP
Clear
LOP
= 47QL * NOT (46QL)
Set LOP includes a three-cycle pickup
delay.
+ NOT (47P) * NOT (
50P
)
=
NOT (47QL) *
47P
The different set and clear conditions ensure that LOP stays latched during subsequent faults,
but is cleared when balanced voltages return. Loss of three-phase potentials due to potential
fuse operation may cause the relay to trip if phase current is above the 50P setting.
You determine how the relay uses loss-of-potential detection by selecting the LOPE setting.
The LOPE setting choices and their associated results are:
N
Rlay sets LOP bit when loss-of-potential condition is detected.
Distance and directional elements are not blocked.
Set the LOP bit in a programmable logic mask to indicate condition, if desired.
Y
Relay sets LOP bit when loss-of-potential condition is detected.
Distance elements are blocked and directional elements default forward.
Set the LOP bit in a programmable logic mask to indicate condition, if desired.
1
Relay blocks distance elements and directional elements default forward when
LOP condition is detected.
If the 52A input is asserted while LOP is detected, the Relay Word LOP bit is
asserted.
If the 52A input is not asserted while LOP is detected, the Relay Word LOP bit
is not asserted.
Set the LOP bit in a programmable logic mask to indicate that a loss-of-poten-
tial has occurred while the breaker is closed, if desired.
2
Relay sets LOP bit when loss-of-potential condition is detected.
Distance elements are blocked and directional elements default forward.
Relay asserts ALARM contact to indicate the LOP condition.
2-16
Specifïcations
SEL-221F, -1 Instruction Manual
Date Code 920817
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...