IF ( Imax >
4 x Imed ) THEN Single-Phase
ELSE IF ( Imed >
4 x Imin ) THEN Two-Phase
ELSE IF ( Ifmax > 1.5 x Ifmed ) THEN Single-Phase
ELSE IF ( Ifmed > 1.5 x Ifmin ) THEN Two-Phase
ELSE IF ( none of the above ) THEN Three-Phase
Where:
Imax = Highest uncompensated phase current
Imed = Second highest uncompensated phase current
Imin = Lowest uncompensated phase current
Ifmax = Highest load compensated phase current
Ifmed = Second highest load compensated phase current
Ifmin = Lowest load compensated phase current
This algorithm is largely immune to load and system grounding variations.
The phase involvement is indicated as one of the following:
AG
:
BG
:
CG
:
AB
:
BC
:
CA
:
ABG :
BCG :
CAG :
ABC :
For A-Phase to Ground faults
For B-Phase to Ground faults
For C-Phase to Ground faults
For A-B Two-Phase faults
For B-C Two-Phase faults
For C-A Two-Phase faults
For A-B Two-Phase to Ground faults
For B-C Two-Phase to Ground faults
For C-A Two-Phase to Ground faults
For Three-Phase faults
The zone and phase involvement data are joined into a single string, completing the TYPE
designation, as in
"
3BG
"
for a Zone 3 B-phase to ground fault.
For event reports triggered by TRIP output assertion, TYPE designation is appended with a
"
T.
"
This aids in determining clearing times for faults that continue after the first event
report ends. For example, if the relay trips for a 3BG fault after completing the initial report,
the second report shows
"
3BGT
"
for TYPE.
Event records taken with no triggering relay elements picked up are labelled as follows:
or
"EXT" for reports triggered externally via input
contacts or "TRIGGER" command execution
"TRIP" for reports triggered by "TRIP" output
contact assertion.
4-4
Event Reporting
SEL221F, -1 Instruction Manual
Date Code 920423
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...