T r o u b l e s h o o t i n g
V115E_09.20
Series-65H Hoist Pos 4
1.
The green pilot lamp (H65) “Ready” is
switched on when the hoist is in work-
ing condition and starts moving when
operated. In this case no other pilot
lamp is switched on.
2.
The yellow pilot lamp (H63) “Overload”
is switched on when the hoist is loaded
with a burden bigger than the nominal
load or the number of persons is ex-
ceeded. Reduce the overload until the
overload pilot lamp is switched off and
the ready for use lamp is switched on.
3.
The red pilot lamp (H66) “Out of ser-
vice” is switched on when for exam-
ple the hoist door is open and thus the
control system’s safety circuit discon-
nected. The hoist must not move when
operated. The more specific reason
for the safety circuit being broken is
shown on the fault diagnostics dis-
play. Remove the cause, for instance
by closing the door. The red pilot lamp
of the safety circuit is switched off and
the ready for use pilot lamp is switched
on. The red pilot lamp of the safety cir-
cuit is also found at the ground station
and on every landing.
In addition there are three pilot lamps on
the cage control panel to show the state
of the hoist.
H65
Ready Overload Out
of service
Cage
light
Alarm
H63
H66
1 2 3
4 5 6
7 8 9
*
0 #
S103
S30
S60.1
EMERGENCY
STOP
60 %
ON
80 %
100 %
cage display
selected floor
call input
+OP2
The most common reasons why
the hoist not moving you can
find in next chapter. Also the
list of faults on the display in the
cage. All possible reasons can
be divided into two categories:
frequency converter faults and
hoist controller faults. Controller
fault can be found in HPG60 de-
vice in menu C3 Fault Log. Fre-
quency converter fault will also
be signalled in HPG60 but full er-
ror will be display on frequency
converter front panel in OP6.
☞
What to do when only H66 is on
•
check information on TFT (cage dis
-
play) in OP2 control box.
•
check the emergency stop, OP1 and
OP2, OP6.
•
reset the system / shout off Q1 for 1
min. Next shout on again.
What to do when H66 and H65 is on
•
check landing gate / cage door
Summary of Contents for 65H Series
Page 2: ...2 T a b l e o f C o n t e n t s Series 65H Hoist Pos 0 V115E_09 20...
Page 10: ...G e n e r a l i n f o r m a t i o n 2 V115E_09 20 Series 65H Hoist Pos 1...
Page 26: ...G e n e r a l i n f o r m a t i o n 18 V115E_09 20 Series 65H Hoist Pos 1 4450 L L1 L2 TWIN...
Page 34: ...G e n e r a l i n f o r m a t i o n 26 V115E_09 20 Series 65H Hoist Pos 1...
Page 36: ...S a f e t y i n s t r u c t i o n s 2 V115E_09 20 Series 65H Hoist Pos 2...
Page 46: ...S a f e t y i n s t r u c t i o n s 12 V115E_09 20 Series 65H Hoist Pos 2 MAX 1000 kg TH_10E...
Page 54: ...S a f e t y i n s t r u c t i o n s 20 V115E_09 20 Series 65H Hoist Pos 2 Tx527...
Page 55: ...21 S a f e t y i n s t r u c t i o n s V115E_09 20 Series 65H Hoist Pos 2...
Page 82: ...O p e r a t i n g i n s t r u c t i o n s 24 V115E_09 20 Series 65H Hoist Pos 3...
Page 84: ...2 V115E_09 20 T r o u b l e s h o o t i n g Series 65H Hoist Pos 4...
Page 124: ...10 V115E_09 20 Service and maintenance Series 65H Hoist Pos 5...
Page 144: ...30 V115E_09 20 Service and maintenance Series 65H Hoist Pos 5 Picture 3c Picture 3b...
Page 154: ...40 V115E_09 20 Service and maintenance Series 65H Hoist Pos 5...
Page 156: ...Inspection forms V115E_09 20 Series 65H Hoist Pos 8 SC HOIST INSPECTION FORMS...
Page 164: ...Inspection forms V115E_09 20 Series 65H Hoist Pos 8 SC HOIST INSPECTION FORMS...