Page 1: ...MREM 81 MTM VR RFID module 125 kHz ...

Page 2: ...voltage 8 28 Vdc Typical current consumption 60 mA 12 V Maximum input power 1 5 W Reading id media EM Marin Jablotron 1x RS 485 system bus APS mini Plus 1x Wiegand external RFID reader GSM module license plate camera 1x Open drain transistor output 30 V 1 A 2x INPUT door contact exit button tamper Integrated in module MTMRFID c Variants Product variants in aluminium silver color CATALOG NUMBER PAR...

Page 3: ...M has its own cabling data bus of the APS mini Plus access system and the power supply can either be used from the MTM panel or have a 12V 24V power bus for the APS mini Plus access system Complete door control lock control open drain door contact input exit button alert notification to PC or Cloud wiegand input system bus power supply The reader module can operate autonomously or as a part of the...

Page 4: ...ion on the RS 485 bus with control from a mobile phone from the WebHit cloud application Up to 32 reader modules can be connected to one APS mini Plus line How to connect in star Using the REP 485 line repeater ...

Page 5: ...indicators 14 5 4 Configurable parameters 15 6 Operating modes 16 6 1 Standard operating mode 16 6 2 External reader with Wiegand output 17 7 Function 18 7 1 Functions of the reader module 18 7 2 Function Door open 18 7 3 Permanent lock release based on valid time schedule 18 7 4 Function of ID with flag 18 7 5 ID expiration 19 7 6 Antipassback function APB 19 7 7 Disabling the reader module 19 7 ...

Page 6: ... Backup 24 h Memory ID media Events Time plans 2000 3400 64 pc Signalization RGB led Piezo 1 1 pc 1 2 Communication interface INTERFACE DESCRIPTION TECHNOLOGY PROPERTIES System data bus RS 485 19 200 bit s 8 data bits even parity 1 stop bit Wiegand Wiegand RS 485 Formats 26 32 34 37 44 46 56 bits custom 1 3 Mechanical parameters PARAMETER MREM 81 MTM MREM 81 MTMVR JEDNOTKA Weight 122 g Dimensions ...

Page 7: ...ta 0 Wiegand reader both sided control 6 Gray IN 2 input 2 configurable funciton Exit button 7 Yellow IN 1 input 1 configurable function Door contact 8 Brown Signal ground 0 V Ground for input signals door contact 9 White Signal B system data bus APS mini Plus system bus 10 Black Signal A system data bus APS mini Plus system bus 2 1 1 Inputs and Outputs INPUT OUTPUT DESCRIPTION Input 1 IN 1 Door c...

Page 8: ... 2 3 1 Radio signal interferences If a 125 kHz reader is used it is necessary to take into account another 125 kHz reader in direct range for example when checking the door on both sides In this case the readers may interfere with each other In the techfass system it is possible to use the so called synchronization of reading between the reader and the reading module which then do not interfere wi...

Page 9: ...ead media on a frequency of 125 kHz like EM Marin e g EM4200 EM4305 Next example of supported media technology is Jablotron ID 125 kHz settings possibilities Default settings for 125 kHz MIFARE a MIFARE Classic are registered trademarks owned by NXP B V Android is registered trademark owned by Google LLC ...

Page 10: ...ck is reverse or standard etc it must be connected to the converter eg APSUSB or APSLAN and use the desktop application APS Reader or to CON 110 IP and use the WebHit application website USECASE B System wise where the individual reader modules are connected to the RS485 bus where up to In this case the reader module is independent on the entry panel it can operate autonomously or as part of the A...

Page 11: ...rly administer or configure the system centrally more reader modules or door controllers are connected in the system we will connect the RS485 system bus Its end is fed into the switchboard and connected to the LAN or the Internet using the APSLAN converter or the CON 110 IP cloud connector USECASE D As part of a modular MTM entry panel easy installation example simply connect the 4 wires of the r...

Page 12: ...www techfass com RFID reader module MREM 81 MTM VR For reverse lock mode just switch the settings in the control software It is necessary to connect the output GND of DC sources VAS 101 and 12 24 Vdc ...

Page 13: ...ty 101 produkt 1355 aps hit The desktop application for administration Small medium installation APS Hit https www techfass com cs produkty 101 produkt 1355 aps hit Medium large APS Administrator https www techfass com en products 101 product 391 aps administrator Web application for configuration administration WebHit https webhit techfass com login 5 2 HW address setting By MREM 81 MTM VR is pos...

Page 14: ...ded hw address 5 3 Meaning of LED indicators COLOR ACTION DESCRIPTION Red Continuously lit Online communication of the RS 485 system bus Flashing with a period of 4 s Offline operation Green Flash ID media reading alternation Red green Red green flashing Address setting mode RS 485 system bus test Yellow Continuously lit flashing Programming mode Short flashing period 1 s Door lock release indicat...

Page 15: ...0 s Forced door alert signalization time 0 255 s 0 s Door ajar alert signalization time 0 255 s 0 s Door ajar allowed opened door time 0 255 s 20 s ID with Alarm flag alert signalization time 0 255 s 0 s Enable exit button in tamper state YES NO YES EVENTS Events archive saving options Door opened input 1 off Door closed input 1 on Input 2 off input 2 on Output 1 off output 1 on ON OFF ON OFF ON O...

Page 16: ... 1 2 Online mode In Online mode the module or more modules on the line are connected to a PC running the relevant application such as APS Hit or APS Administrator or the line is connected to the cloud using CON 110 IP and the administrator works in the WebHit web application In this case each event is immediately written to the application 6 1 3 Online authorization The APS mini Plus system implem...

Page 17: ...eader mode with Wiegand output in the following formats 6 2 1 125 kHz Enable Disable options Standard em marin proprietary tf ID Jablotron ID Default settings All enabled ID length 125 kHz bits ID length 24 32 40 44 56 Default settings 40 bits format Wiegand output setting 125 kHz bits Data length 26 32 42 44 56 Default settings 42 bits format ...

Page 18: ... output remains unchanged until the next activation of the Door open function In the case of the pulse lock control mode after activating the Door open function the relay output is activated for the time given by the parameter Pulse width ms In the case of the standard lock control mode reading a valid card during lock activation will cause a new lock timing Online authorization If the reader modu...

Page 19: ...ress Enable door opening after time APB alarm if the function is enabled the Door opening function is started in case of time APB alarm 7 6 2 Zone antipassback Zone antipassback is defined by enabling disabling this feature The zone antipassback flag is set for the user after passing Upon further identification a Zone antipassback alarm is triggered in the case of a flag set for the given ID The f...

Page 20: ...tween individual types alarms The alarm condition is terminated by restoring all idle conditions closing the door fitting the cover etc 7 8 1 Tamper The MREM 81 NO IGBKP reader module is not equipped with a Tamper sensor to detect that the lid is open 7 8 2 Forced door The Forced door status occurs when the IN1 input of the module is opened without first activating the Door open function The only ...

Page 21: ... of programming cards and cards It does not enter the programming mode while waiting for the card confirming the address setting for modules with address setting via the communication line The behavior of the modules in the programming mode is evident from figures below When inserting cards using programming cards it is not possible to work with time schedules so the cards are still valid VALID UN...

Page 22: ...s back into standard operating mode Deleting cards 7 10 3 Deleting cards above or below If a user loses his ID medium it is usually impossible to delete the ID from the memory with the procedure described in the previous chapter since the medium is no longer available with an exception of entering the code at the keypad Following procedure can be used for deleting such ID The procedure requires us...

Page 23: ...all cards 7 10 5 Recommended method for access rights management using prog cards In case of managing access rights of plenty of users using programming cards only it is appropriate to establish a table which summarizes operation with the reader module memory All operations adding and deleting cards should be stored in the table Following example shows correct usage of the programming cards and pr...

Page 24: ...ure from chapter 6 7 1 again 1 Read inserting programming card read cards 1 5 after 15 s the programming mode is exited Register the change in your table Table after inserting card 6 A new card is always inserted at the position after the last inserted card In case of deleting all cards using the procedure described in chapter 7 10 4 it is necessary to create a new filing table position card 1 car...

Page 25: ... 8 2 Declaration of conformity The manufacturer TECH FASS ltd declares that the product follows legal requirements and fulfils necessary European directives The declaration of conformity document can be downloaded from our web site https www techfass com en download 11 conformity declaration 8 3 Electrical waste According to WEEE directive 2012 19 EU this product cannot be disposed of as unsorted ...

Page 26: ...TECH FASS s r o Věštínská 1611 19 Praha ...