Step 3: Through-hole Current Wiring of Accura 2350-1P3FSC
Item
Description
Connector type
Through-hole type
Wire specification Varies by the hole size
Measuring range
Model
Basic Current Measuring Range
(Accuracy Guaranteed
3
)
Min. Measured
Value
Accura 2350-1P3FSC-125A
125 A
1.25 A -
150 A
0.83 A
Accura 2350-1P3FSC-125A-DIZCT
125 A
1.25 A -
150 A
0.83 A
Accura 2350-1P3FSC-60A
60 A
0.60 A -
72 A
0.40 A
Accura 2350-1P3FSC-60A-DIZCT
60 A
0.60 A -
72 A
0.40 A
Measurement
Current
±
0.5 % Reading
1
accuracy
Active power
IEC 61557-12 Class 0.5
Active energy
IEC 62053-22 Class 0.5S
Impedance
Not applicable since the model is a through-hole type device
Frequency range
42
–
69 Hz
Hole dimensions
Model
Hole Dimensions
Weight
/Weight
Accura 2350-1P3FSC-125A
16.6 x 21.8 mm
457 g (excluding mounting wings)
Accura 2350-1P3FSC-125A-DIZCT
16.6 x 21.8 mm
468 g (excluding mounting wings)
Accura 2350-1P3FSC-60A
11.8 x 21.8 mm
393 g (excluding mounting wings)
Accura 2350-1P3FSC-60A-DIZCT
11.8 x 21.8 mm
404 g (excluding mounting wings)
Mounting wing
4 g
1. The maximum measurement error of
±
1 % may occur according to the position of the hole through which cables
pass.
Caution
It is recommended you should use CTT terminal blocks in order to prevent accidents caused by
current transformers and identify device failures in advance. If current is flowing in the primary
winding of a CT, opening the CT secondary can cause serious accidents resulting from high voltages.