Chapter 4 Accura 2300S Operation/Setup
Accura 2300S/2350-1P3FSC User Guide
Page 92
ⓒ
2015 Rootech Inc. All Rights Reserved
Measurement Setup
Voltage Connection
Setup Range
Description
3P4U (default)
3-phase 4-wire (3P4W)
3P3U
3-phase 3-wire (3P3W)
1P3U
Single-phase 3-wire (1P3W)
1P2U
Single-phase 2-wire (1P2W)
3P3O
1
3-phase 3-wire Open-Delta (3P3O)
1.
「
3P3O
」
is the setup menu for old Accura 2300S models that do not support the 3P3W connection mode. Thus,
even if the connection mode is set to 3P3O, it works in the same way as the 3P3W connection mode.
PT Rating
The ratio of primary to secondary line-to-line voltages is used as the conversion ratio for the primary
voltage. Regardless of the voltage connection mode for measurement, the primary and secondary line-
to-line voltage values of the PT should be input all the time.
Setup Range
Description
Pr[d][d][d][d][d][d]
1
PT primary line-to-line voltage rating
000001
–
999999
1
–
999,999 V
(default 380)
Sc[d][d][d]
1
PT secondary line-to-line voltage rating
001
–
999
1
–
999 V
(default 380)
1. d
→
decimal
The primary and secondary line-to-line voltages for each connection mode is configured as follows. In
case of direct connections without using a PT, the same values should be input as the primary and
secondary line-to-line voltage values.
Fig 4.18 3-phase 4-wire Connection(3P4W): Setup for PT Primary V
L12
& Secondary V
12