Chapter 3 Accura 2350 Operation/Setup
Accura 2300S/2350-1P3FSC User Guide
Page 74
ⓒ
2015 Rootech Inc. All Rights Reserved
Leakage Current(Threshold Value) Measurement Setup for Feeder 3
Item
Description
C
1
: the phase of the feeder
passing through the ZCT
oFF, 20
–
990 mA
(default: 200)
oFF : Measurement deactivated
20
–
990 mA : the threshold value of leakage
current
1. It applies when the C phase is selected in line-to-neutral connection mode.
Leakage Current Event Setup
Leakage current measurement is supported only on Accura 2350-1P3FSC-DIZCT module.
Leakage current events can be set when the leakage current measurement function is enabled. If the
leakage current measurement item is set to
「
oFF
」
, setup values for leakage current events are invalid. If
the leakage current event item is set to
「
on
」
, the event is processed through the event log of Accura
2300S when the measured leakage current exceeds the threshold value and the event occurs. Leakage
current event settings are commonly applied to all ZCTs installed on the feeder 1, 2 and 3.
You can set leakage current events through Accura 2300S
’
LCD screen or communication. Event setup via
Accura 2300S is commonly applied to all Accura 2350 modules connected to Accura 2300S. If you want
to set a different leakage current event for each Accura 2350 modules, you should set the event
individually through the SET button on Accura 2350 modules.
Item
Description
oFF[default]
Event detection disabled
on
Event detection enabled