Chapter 4 Accura 2300S Operation/Setup
Accura 2300S/2350-1P3FSC User Guide
Page 132
ⓒ
2015 Rootech Inc. All Rights Reserved
Dip Event Log
Dip Start Event Log
Display
Description
E[d][d][d]
1
Event log number 000 - 999
A dIP.S
Dip start event occurs on A phase.
2
[d][d][d][d] V
Voltage [V] measured when a dip start event occurs
1. d
→
decimal
2. It indicates the information on the phase or line-to-line where the event occurred. In 3P4W mode, the phase(A, B,
C) is displayed, but in 3P3W mode, the line-to-line(AB, BC, CA) voltage is displayed.
Dip End Event Log
For the dip event that occurred, the duration and the minimum voltage measured during the event
are displayed.
Display
Description
E[d][d][d]
1
Event log number 000 - 999
A dIP.E
Dip end event occurs on A phase.
2
[d][d][d][d] V
Minimum voltage[V] measured during the voltage dip
event
[d][d][d][d][d] ms
Dip duration time [ms]
1. d
→
decimal
2. It indicates the information on the phase or line-to-line where the event occurred. In 3P4W mode, the phase(A, B,
C) is displayed, but in 3P3W mode, the line-to-line(AB, BC, CA) voltage is displayed.
Swell Event Log
Swell Start Event Log
Display
Description
E[d][d][d]
1
Event log number 000 - 999
A SuL.S
Swell start event occurs on A phase.
2
[d][d][d][d] V
Voltage[V] measured when a swell start event occurs
1. d
→
decimal
2. It indicates the information on the phase or line-to-line where the event occurred. In 3P4W mode, the phase(A, B,
C) is displayed, but in 3P3W mode, the line-to-line(AB, BC, CA) voltage is displayed.