Digital Input/Output Setup
Digital Input Status
Digital Input Status
Description
_
Displays the contact is open
ㅁ
Displays the contact is closed
Simultaneously displays the status of channel 1 and channel 2 from the left.
Digital Output Type
Setup Range
Description
Latch(default)
1
Latch type
PuLS.U(Pulse Uncounted)
1
Uncountable pulse type
2
PuLS.C(Pulse Counted)
1
Countable pulse type
2
P.PuLS(Periodic Pulse)
1
Periodic pulse type
2
1. The operations for various digital outputs are as follows.
Output Type
Command Operation
3
Latch
1
Maintains the closed status of the contact.
0
Maintains the open status of the contact.
Uncountable
pulse
1
A single pulse occurs when the contact is closed. If an additional
command is issued within the pulse period, the command is ignored.
0
Not available
Countable
pulse
1
A single pulse occurs when the contact is closed. A command issued after
the pulse is generated is automatically cleared.
Additional commands issued within the pulse period are counted, and
additional pulses occur after the pulse period ends.
0
Not available
Periodic pulse 1
Periodic pulses continue to occur when the contact is closed.
0
Pulses no longer occur after the occurrence of periodic pulses is stopped
when the contact is closed.
2. The duty cycle of a pulse features the pulse period and the pulse on time.
3. It applies when the polarity of the output is set to
「
normal
」
. If
「
Reverse
」
is selected, the closed
contact and the open contact operate reversely.