Accura 2300S/2350-1P3FSC User Guide
Chapter 5 Measurements
ⓒ
2015 Rootech Inc. All Rights Reserved
Page 151
Measurement of Voltage Dips(Sags)/Swells
1 Cycle RMS Measurement with Half-cycle Sliding Window
Accura 2300S measures the RMS voltage over 1 cycle using a half-cycle sliding window. The time
resolution for the RMS value measured over 1 cycle is one half cycle. Dips(Sags)/Swells are detected
based on the RMS value measured over 1 cycle.
Fig 5.5 Calculation of 1-cycle RMS Voltage Refreshed Each Half Cycle
Half-cycle refreshed 1-cycle RMS
220.0 173.8 110.0 110.0 110.0 173.8 220.0 220.0
Dip(Sag)/Swell Detection
As it is defined in IEC 61000-4-30, voltage dips(sags)/swells are detected by measuring 1-cycle RMS
values refreshed each half cycle. The time resolution for dip(sag)/swell detection is one half cycle.
Fig 5.6 Voltage Dip(Sag) Detection
1-cycle RMS
220.0
173.8 110.0 110.0 110.0 173.8
220.0 220.0
220.0
Dip theshold = 180.0
Dip start time
Dip end time
Dip duration
Dip end voltage
Dip start voltage
Dip peak voltage (Max. Residual Voltage)