Appendix B Standards Compliance
Accura 2300S/2350-1P3FSC User Guide
Page 170
ⓒ
2015 Rootech Inc. All Rights Reserved
Calculated Neutral Current (from phase currents)
PMD Types
Phase Current
Range
Minimum Bandwidth
(Harmonic)
Crest Factor
Class 0.2
Class 0.5
PMD Sx
10 % In
–
Imax
45 Hz to 15 times the
rated frequency
2
±
0.2 %
1
±
0.5 %
1
PMD Dx
20 % Ib
–
Imax
1. Uncertainty is indicated as a percentage of the largest phase current value.
Measured Neutral Current (with a sensor)
PMD Types
Neutral Current
Range
Minimum Bandwidth
(Harmonic)
Crest Factor
Class 0.2
Class 0.5
PMD Sx
10 % In
–
Imax
45 Hz to 15 times the
rated frequency
2
±
0.2 %
±
0.5 %
PMD Dx
20 % Ib
–
Imax
RMS Voltage
Voltage Range
Minimum Bandwidth (Harmonic)
Crest Factor
Class 0.5
Umin
–
Umax
45 Hz to 15 times the rated frequency
1.5
±
0.5 %
Power Factor
Voltage Range
Current Range
Power Factor
Class 0.5
PMD Dx
PMD Sx
50 % Un
–
Umax
20 % Ib
–
Imax
10 % In
–
Imax
0.5 inductive
–
0.8 capacitive
±
0.005
1
1. There is no unit for the value.