Accura 2300S/2350-1P3FSC User Guide
Chapter 4 Accura 2300S Operation/Setup
ⓒ
2015 Rootech Inc. All Rights Reserved
Page 123
Event Parameters in Countable Pulse Mode
This setup screen is displayed in case that the digital output type is set to the countable pulse mode. If
you select the accumulated energy to associate with the digital output and set the accumulated energy
scale per pulse, the output pulse is automatically generated every time the accumulated energy per
pulse increases.
Selectable energy parameters are as follows.
Setup Range
Description
no(No Parameter, default)
No selection
r
ㅏ
Wh
Associated with received active energy
d
ㅏ
Wh
Associated with delivered active energy
r
ㅏ
Urh
Associated with positive reactive energy
d
ㅏ
Urh
Associated with negative reactive energy
Accumulated Energy Scale per Pulse
The ratio of the accumulated energy per pulse is set, and output pulses are automatically generated
according to this ratio.
When the energy scale is set to kWh via
「
METER > Enrg ScaL(Energy Scale)
」
menus, the energy value
increases with a resolution of 1 kWh. Therefore, if the accumulated energy scale per pulse(do ScaL) is
set to a value less than 1.00, multiple pulses can be output at once when the energy increases by 1
kWh. That is, when the energy scale is set to 0.1, 10 pulses are output at once when the energy
increases by 1 kWh.
When the energy scale is set to Wh via
「
METER > Enrg ScaL(Energy Scale)
」
menus, the energy value
increases with a resolution of 1 Wh. Therefore, if the accumulated energy scale per pulse(do ScaL) is set
to a value less than 1.00, multiple pulses can be output at once when the energy increases by 1 Wh.
That is, when the energy scale is set to 0.1, 10 pulses are output at once when the energy increases by
1 Wh.
If the scale is set to a too small value, pulses cannot be generated properly when the energy value
rapidly increases. Therefore, it is necessary to set the scale to an appropriate value to obtain proper
digital outputs according to an increase in energy usage.
Setup Range
Description
[d][d].[d][d]
1
(default 1.00)
0.01 - 99.99
Unit: kWh, kVARh when energy unit is set to
kWh
Unit: Wh, VARh when energy unit is set to
Wh
1. d
→
decimal number