Device Connection for Dedicated Communication
Number of Accura 2350 modules connected to Accura 2300S Max. 15/port
3
6C telephone line length
Max. 6 m/port
4
Connector type
RJ12
Communication port
Accura 2300S
2 ports(RJ12-1, RJ12-2)
5
Accura 2350
2 ports(RJ12A, RJ12B)
6
1. If the rated current exceeds 250 A, you should use Accura 2350-3P-CT5A-75 or Accura 2350-3PSC-CT5A-90
module with external CTs(the secondary current rating: 5 A).
2. It is provided with the product. 4C telephone lines cannot be used. The conducting wire of the 6C telephone line
should be at least 0.128 mm
2
(26 AWG). It is recommended to keep
a distance of over 5 mm from power lines generating high levels of noise to prevent interference.
3. Up to 15 Accura 2350-3P/1P power measuring modules can be connected to each port(RJ12-1, RJ12-2) on Accura
2300S. For details about how to connect Accura 2300S to special-purpose modules, refer to the individual
user manuals of special-purpose modules.
4. It indicates the maximum length of the 6C telephone line used to connect Accura 2300S to all Accura 2350
modules with each port(RJ12-1 or RJ12-2) on Accura 2300S.
6. The RJ12A and RJ12B ports have the same functions.