Chapter 4 Accura 2300S Operation/Setup
Accura 2300S/2350-1P3FSC User Guide
Page 104
ⓒ
2015 Rootech Inc. All Rights Reserved
End Threshold for Current Event
A current event ends when the measured current value falls back below the end threshold. You can set
a hysteresis value between the start and end thresholds to prevent multiple events from occurring
during a short period of time, and the minimum hysteresis value is 1 %. In other words, the end
threshold can be set to a value at least 1 % less than the start threshold. If the start threshold is set to
a value less than the end threshold, the end threshold is automatically reset to a value 1 % less than
the start threshold.
Setup Range
Description
0.0 - 998.0 % (default 98.0 %) End threshold expressed as a percentage
The reference current for the percentage is the rated current of each Accura
2350 module. Commonly applied to all Accura 2350 modules.
Delay Time for Current Event
A current event starts when the measured current value rises above the start threshold and is
maintained during the delay time for the event.
Setup Range
Description
0, 1
–
999 (default 1)
Delay time for the current event [s]
0: If it is set to 0, it indicates that the delay time is 0.5 seconds.
Commonly applied to all Accura 2350 modules
Leakage Current Event
When the leakage current event item is set to on, the screen that lets users set the start threshold
and delay time for the leakage current event appears. If the leakage current event item is set to off, the
screen switches to the demand current event setup screen.
Setup Range
Description
All.oFF (default)
Event detection disabled
All.on
Event detection disabled
no.SEL
Exit the edit mode and navigate to the
previous setup mode.
Commonly applied to all Accura 2350 modules.
Users can set on or off status on each Accura 2350 module.