Fuse Fail Event
When the voltage value measured on each phase is zero and the measured current is a non-zero value,
it is deemed that a fuse failure occurs on the line where voltage is measured. A fuse fail event starts
when a fuse failure is detected, and the event ends when the fault condition is removed.
Setup Range
Description
oFF (default)
Event detection disabled
on
Event detection enabled
Temperature Event
Temperature measured by the temperature sensor at the rear of Accura 2300S differs depending on the
number of Accura 2350 modules connected to Accura 2300S. The measured temperature is different
from the actual temperature in the distribution panel, thus caution is required when setting the
temperature event. When the temperature event item is set to on, the screen that lets users set the
start temperature and end temperature thresholds appears. If the temperature event item is set to off,
the screen directly switches to the current event setup screen.
Setup Range
Description
oFF (default)
Event detection disabled
on
Event detection enabled
Start Threshold for Temperature Event
A
temperature event starts when the measured temperature goes above the start temperature
threshold.
Setup Range
Description
20 - 9999
℃
(default 50
℃
)
Temperature threshold for detection of the
start of an event