End Threshold for Temperature Event
A temperature event ends when the measured temperature falls back below the end threshold of the
event. You can set a hysteresis value between the start and end thresholds to prevent multiple events
from occurring during a short period of time, and the minimum hysteresis value is 1
o
C. In other words,
the end threshold can be set to a value at least 1
o
C less than the start threshold. If the start threshold
is set to a value less than the end threshold, the end threshold is automatically reset to a value 1 % less
than the start threshold.
Setup Range
Description
0 - 9998
℃
(default 48
℃
)
Temperature threshold for detection of the
end of an event
Current Event
When the current event item is set to on, the screen that lets users set the start threshold, end
threshold, and delay time for the current event appears. If the current event item is set to off, the
screen immediately switches to the leakage current event setup screen.
Setup Range
Description
oFF (default)
Event detection disabled
on
Event detection enabled
Commonly applied to all Accura 2350 modules.
Start Threshold for Current Event
A
current event starts when the measured current value goes above the start threshold and is
maintained during the set delay time for the current event.
Setup Range
Description
5.0 - 999.0 % (default 100.0 %) Start threshold expressed as a percentage
The reference current for the percentage is the rated current of each Accura
2350 module. Commonly applied to all Accura 2350 modules.