Accura 2300S/2350-1P3FSC User Guide
Chapter 4 Accura 2300S Operation/Setup
ⓒ
2015 Rootech Inc. All Rights Reserved
Page 133
Swell End Event Log
For the swell event that occurred, the duration and the maximum voltage measured during the event
are displayed.
Display
Description
E[d][d][d]
1
Event log number 000 - 999
A SuL.E
Swell end event occurs on A phase.
2
[d][d][d][d] V
Maximum voltage [V] measured during the voltage
swell event
[d][d][d][d][d] ms
Swell duration time [ms]
1. d
→
decimal
2. It indicates the information on the phase or line-to-line where the event occurred. In 3P4W mode, the phase(A, B,
C) is displayed, but in 3P3W mode, the line-to-line(AB, BC, CA) voltage is displayed.
Fuse Fail Event Log
Fuse Fail Start Event Log
Display
Description
E[d][d][d]
1
Event log number 000 - 999
A FuSE
Fuse fail start event occurs on A phase.
2
Strt
Start event
1. d
→
decimal
2. It indicates the phase(A, B, C) where the event occurred.
Fuse Fail End Event Log
Information on the fuse fail end event is displayed.
Display
Description
E[d][d][d]
1
Event log number 000 - 999
A FuSE
Fuse fail end event occurs on A phase.
2
End
End event
[d][d][d][d][d] ms
Fuse fail duration time [ms]
1. d
→
decimal
2. It indicates the phase(A, B, C) where the event occurred.