Leakage Current(Threshold Value) Measurement Setup for Feeder 1
Leakage current measurement is supported only on Accura 2350-1P3FSC-DIZCT module.
If the leakage current measurement item is set to
「
oFF
」
, the leakage current measurement function is
disabled and the measured value is not displayed. When the threshold value of leakage current is set,
leakage current is measured, and the measured value is displayed. The device also detects the leakage
current event based on the set threshold value and processes the event through the event log
according to the event settings on Accura 2300S.
The threshold value of leakage current can also be set through the LCD screen of Accura 2300S or
communication. The threshold value set through Accura 2300S is applied equally to all Accura 2350
modules connected to Accura 2300S. If you want to set a different threshold value for each Accura 2350
module, you should set the value individually through the SET button on Accura 2350 modules.
Item
Description
A
1
: the phase of the
feeder passing through the
ZCT
oFF, 20
–
990 mA
(default: 200)
oFF : Disables the leakage current measurement
function
20
–
990 mA : the threshold value of leakage
1. It applies when the A phase is selected in line-to-neutral connection mode.
Leakage Current(Threshold Value) Measurement Setup for Feeder 2
Item
Description
B
1
: the phase of the feeder
passing through the ZCT
oFF, 20
–
990 mA
(default: 200)
oFF : Disables the leakage current
measurement function
20
–
990 mA : the threshold value of leakage
current
1. It applies when the B phase is selected in line-to-neutral connection mode.