Chapter 4 Accura 2300S Operation/Setup
Accura 2300S/2350-1P3FSC User Guide
Page 106
ⓒ
2015 Rootech Inc. All Rights Reserved
Start Threshold
for Demand Current Event
A demand current event starts when the measured demand current value rises above the start
threshold for the demand current event.
Setup Range
Description
5.0
–
999.0 % (default 70.0 %)
Start threshold for the demand current
event expressed as a percentage
The reference current for the percentage is the rated current of each Accura
2350 module. Commonly applied to all Accura 2350 modules
Power Event
The power event detection function can be enabled by selecting the event for all three phases or each
phase. If each phase is selected, the event is detected for the power value measured on each phase. If
all three phases are selected, events are detected for the total power value measured on all phases.
Setup Range
Description
oFF(default)
Event detection disabled
Pha.on
Detection of the power event per phase
tot.on
Detection of the power event for all
phases
Start Threshold for Power Event
A power event starts when the measured power value rises above the start threshold for the power
event and is maintained during the set delay time for the event. The start threshold for the power
event can be set to a percentage or power value.
Setup Range
Description
5.0
–
999.0 %
(default 100.0 %)
Percentage of the reference power
The reference power for the percentage is obtained by multiplying the rated
voltage by the rated current of each Accura 2350 module.
Commonly applied to all Accura 2350 modules
In each voltage connection mode, the reference power is determined by the reference voltage as
follows. The reference voltage can be set via
「
METER > UrEF(Reference Voltage)
」
setup menus.