Protective
function
Error code No.
Causes
Measures
Main Sub
6-6
1. When in Trouble
Protective function (Detail of error code)
Over-load
protection
16
0
Torque command value has exceeded
the over-load level set with Pr5.12
(Setup of over-load level) and resulted in
overload protection according to the time
characteristics (described later)
1) Load was heavy and actual torque has
exceeded the rated torque and kept
running for a long time.
2) Oscillation and hunching action due to
poor adjustment.
Motor vibration, abnormal noise.
,QHUWLDUDWLR3UVHWXSHUURU
3) Miswiring, disconnection of the motor.
4) Machine has collided or the load has
gotten heavy. Machine has been
distorted.
5) Electromagnetic brake has been kept
engaged.
6) While wiring multiple axes, miswiring
has occurred by connecting the motor
cable to other axis.
7KHRYHUORDGSURWHFWLRQWLPHFKDUDFWHULVWLFVDUHGHVFULEHGRQ3
Caution
2QFHWKLVHUURURFFXUVLWFDQQRWEHFOHDUHGDWOHDVWIRUVHF
Check that the torque (current) does not
RVFLOODWHVQRUÁXFWXDWHXSDQGRZQYHU\
much on the analog outoput and via
communication. Check the over-load alarm
display and load factor with the analog
outoput and via communication..
1) Increase the capacity of the driver
and motor. Set up longer acceleration/
deceleration time. Lower the load.
2) Make a re-adjustment.
3) Make a wiring as per the wiring diagram.
Replace the cables.
4) Remove the cause of distortion. Lower the
load.
5) Measure the voltage between brake
terminals. Release the brake
6) Make a correct wiring by matching the
correct motor and encoder wires.
*
Over-
regeneration
load
protection
18
0
Regenerative energy has exceeded the
capacity of regenerative resistor.
1) Due to the regenerative energy during
deceleration caused by a large load
inertia, converter voltage has risen,
and the voltage is risen further due to
the lack of capacity of absorbing this
energy of the regeneration discharge
resistor.
2) Regenerative energy has not been
DEVRUEHGLQWKHVSHFLÀHGWLPHGXHWRD
high motor rotational speed.
3) Active limit of the external regenerative
UHVLVWRUKDVEHHQOLPLWHGWRGXW\
Caution
Install an external protection such as thermal fuse without fail when
\RXVHWXS3UWR2WKHUZLVHUHJHQHUDWLYHUHVLVWRUORVHVWKH
protection and it may be heated up extremely and may burn out.
Check the load factor of the regenerative
resistor from the front panel or via communi-
cation.
Do not use in the continuous regenerative
brake application.
1) Check the running pattern (velocity
monitor). Check the load factor of the
regenerative resistor and over-regeneration
warning display. Increase the capacity
of the driver and the motor, and loosen
the deceleration time. Use the external
regenerative resistor.
2) Check the running pattern (speed monitor).
Check the load factor of the regenerative
resistor. Increase the capacity of the driver
and the motor, and loosen the deceleration
time. Lower the motor rotational speed.
Use an external regenerative resistor.
6HWXS3UWR
Note
Related page
:KHQSURWHFWLYHIXQFWLRQPDUNHGZLWK
*
in the protective function table is activated, it can-
not be disabled by the alarm clear input (A-CLR). To return to the normal operation, turn off
power, remove the cause, and then turn on power again.
3´'HWDLOVRISDUDPHWHUµ
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for MINAS A5 Series
Page 164: ...2 116 MEMO Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 280: ...4 64 MEMO Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 322: ...5 42 MEMO Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 350: ...6 28 MEMO Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...