Connecting the GT to a PLC
GTWIN Reference Manual
278
Word device (see p.
293
)
Address
Input relay
WX0000-WX511F
Output relay
WY0000-WY511F
Internal relay
WR0000-WR886F
Link relay
WL0000-WL639F
Data register
DT00000-DT10239
Link register
LD0000-LD8447
Timer/Counter set value area
SV0000-SV3071
Timer/Counter elapsed value area
EV0000-EV3071
Special data register
DT90000-DT90511
If you enter a value that is out of range on the GT side, GTWIN will issue an
error message.
The address range actually available depends on the specific PLC model.
Please refer to the PLC manual for details.
Communication parameters, example settings
The baud rate must be set to 115200bps.
Setting values for GT:
Item
Setting
Baud rate
115200bps
Data length
8
Stop bits
1
Parity bit
Odd
Setting values for the PLC
Item
Setting
Communication mode
MEWTOCOL-COM Slave [Computer Link]
Station no.
1
Baud rate
115200bps
Data length
8
Stop bits
1
Parity
Odd
Start code
No STX