4.7.9.2 Log File Setup
Basic setup tab
Field
Description
File name
Specify file name if desired.
Comment
Add a comment if desired.
Trigger setting
A CSV file with the characters "SET" (see "Log File and CSV File Structure" on
p. 171) will be recorded when the conditions for this dialog are met.
Fixed cycle
The trigger will be executed in a fixed cycle.
Specified time
Specify the start time for logging, the intervals between each log and the no. of
logs to record.
"Start time" means o'+ CHAR(39) + 'clock, e.g. 1 Hour 30 Min. = 1:30 a.m.
Condition
The trigger will be executed when the conditions specified are met.
Create Logging File After ...
The settings for this field determine when the data in the SRAM is written as files
to the SD memory card. The settings available depend on what you have
specified for the trigger setting.
Restrictions: the same settings can be used for multiple logging files. However,
a 1-second trigger can only be set for 1 file. Triggers at intervals of less than 10
seconds can be set for a maximum of 2 files.