E-022-4-E
9
3.10.4 Download
*
Download :
One complete file data is transferred to the flowmeter transmitter. This permits the setup data of one
flowmeter to be transferred to another to duplicate the setup information of the former.
①
By confirming the parameters currently present in the flowmeter, make sure that the flowmeter is the
one subject to downloading before you start downloading.
If you want to save the parameters, follow the instructions outlined in
"
3.0.2 Save File.
"
②
Select from the drop
-
down list the disk and folder which has the file subject to downloading.
③
Click on the file you want to download. Make sure of
"
Folder name (N)
"
and click on
"
Open (D) button.
④
On seeing a message box like the one shown in Fig. 126, click on "OK" button if you want to download
the data into the transmitter.
If you do not want to download, click on "Cancel" button.
Filename is shown.
Click here and select
the disk and folder
which has the fil to be
download.
Click "Open" button.
Fig.2
Click on the icon of
the file you want to
download.
⑤
Downloading the data will result in changes in parameter settings. The output levels from the flowmeter
will also change accordingly. For safety's sake, therefore, it is suggested that the control loop be
switched to manual to avoid possible influence of output variation.