![background image](http://html1.mh-extra.com/html/omron/nt620c/nt620c_operation-manual_744559286.webp)
7-3
Section
Maintenance of the NT620S/620C
276
Operation
1. Keep the power ON for at least 1 minute and then turn it OFF.
Note
Unless the power is kept ON for at least 1 minute, the memory contents cannot
be retained for more than 5 minutes without a battery.
2. Turn off the power to the NT620S/620C and remove the lid of the CFL case,
located at the upper right part of the rear of the NT620S/620C: remove the
screw with a Philips head screwdriver, then open the CFL case lid.
CFL case lid
Screw securing CFL case lid
3. Pull out the battery together with the connector.
4. Install a new battery.
Insert the battery connector, keeping it straight.