![background image](http://html1.mh-extra.com/html/omron/nt620c/nt620c_operation-manual_744559229.webp)
5-3
Section
Lamps and Touch Switches
218
S
Important Points
Details on touch switch notification operations are tabled below.
Type of notification
operation
When using host link
When using NT link (DM
area)
When using NT link
(other than DM area)
Momentary
(1) Notification in word units
(all other bits in the word
are OFF)
(3) Notification in bit units
Alternate
Set
Reset
(2) Notification in word units
(note that the word con-
tents are read on display
and notification is based
on these contents)
(4) Notification in bit units
When using touch switch input notification, note the following points.
- In the case of (1) in the table, the other bits in the same word are turned OFF
by notification.
Bits other than notify
bits are set to 0
(OFF).
0
1
0
1
0
0
0
1
15 14
0
1
15 14
0
1
Bit
Bit
Press the
touch switch
Touch switch
notify bit
In the case of (2) in the table, since notification is executed on the basis of the
contents of the word before display, the other bits in the word are not overwrit-
ten. However, if the contents of the word are changed at the PC during dis-
play, they will be rewritten based on the contents before display.
- If the screen is switched while a momentary key is pressed, the touch switch
itself will disappear and the “OFF” status will be notified to the PC. This
means that, in the case of (1) in the table, all the bits in the word will be set to
the “OFF” status.
- When using the host link, or when using the NT link with the DM area, the
notification operation is different for the momentary type and the other types,
and they should not both be specified in the same word.
In the case of (3) and (4), notification has no effect on the other bits in the word.
Application
This example uses the touch switches as normal switches (bits) in order to use
the NT620S/620C as an operating panel.
S
Support tool settings
Make the following settings using the support tool.
Touch switch No. 10:
Function “Notify Bit”
Display attribute “Light”
Lamp bit CH05000 (Run flag) ... Guide message: “RUN”
Notify bit CH 06000
Touch switch No. 11: