![background image](http://html1.mh-extra.com/html/omron/nt620c/nt620c_operation-manual_744559185.webp)
4-10
Section
Pop-up Window Function
173
- By registering multiple screen switching keys (touch switches), menus for
screen switching can be created.
When “Graph” is pressed
When “Next”
is pressed
Press here
Graph
Next
MENU
MENU
MENU
MENU
Window Screens and Display Elements
Using the pop-up window function, windows can be created in the screens num-
bered 1900 to 1979 (note that a screen for which a window is registered is called
a “window screen”). Screens other than these cannot be opened as windows.
On returning to the “Screen List” screen after creating a window in the screen
number range 1900 to 1979, specify the “window area (display area)” (The win-
dow will then open in a display area of the specified size and at the specified posi-
tion).
The following elements can be displayed in NT620S/NT620C windows. If ele-
ments other than these are registered on a window screen, they will not be dis-
played when the window opens.
- “Background color” screen attribute (NT620C only)
- Fixed displays
- Touch switches (but the input notification and screen print functions cannot
be used)
- Numeral/character-string input setting fields (only one can be used)
Elements that project beyond the display area will not be displayed when the win-
dow opens. Similarly, display elements on the base screen that overlap even
partly with the window will be deleted when the window opens.
Note
- Since the pop-up window function and screen print function share the same
memory area, it is not possible to open a window during screen printing. Con-
versely, a screen cannot be printed while a window is open.
- The display elements in a window cannot be notified to the PC. This means
that the lamp bits of touch switches in windows cannot be controlled.
- While a window is open, display processing may be slightly delayed.