Appendix A
Specifications
286
* When NT-AL001 used
[For a Memory Link]
Item
Specification
Communications standard
EIA RS-232C
RS-422A*
Communication settings
Start-stop synchronization
Baud rate
: 2400, 4800, 9600, 19200 bps
Data length : 7, 8 bits
Stop bit
: 1, 2 bits
Parity
: None, even, odd
Flow control : None, RS/CS, XON/XOFF
(RS-CS can only be selected with RS-232C.)
Connector
9-pin D-SUB connector (female)
9-pin D-SUB connector (female)
(NT620S/NT620C)
Number of units connected
1:1
Transmission distance
Max. 15 m
RS-232C cable: Max. 15 m
RS-422A cable: Total length 500 m
* An RS232C/RS422 converter unit is required.
Summary of Contents for NT620C
Page 1: ...Cat No V033 E1 5 Programmable Terminals NT620S 620C OPERATION MANUAL...
Page 2: ...NT620S 620C Programmable Terminals Operation Manual Revised April 2001...
Page 3: ...iv...
Page 5: ...vi...
Page 328: ......
Page 329: ......