3-5
Section
Setting the Conditions of Communications with the PC by Using the Memory Switches
75
To set and quit the menu, press “Quit”. The final settings made will be set and the
screen will return to the maintenance mode menu.
3-5-4 Setting the Communication Conditions for Memory Link
When connecting the NT620S/NT620C to the host by the memory link method,
set the communication conditions with the memory switches.
In order to use the memory link method, the dedicated system program must be
installed.
Select the communication conditions from the following in accordance with the
host used.
Item
Setting
Baud rate
2400, 4800, 9600, 19200 bps
Data bit length
7/8 bits
Stop bit length
1/2 bits
Parity
None/even/odd
Flow control
None, RS/CS, XON/XOFF
Response
No, Yes
(Sets whether or not a response is re-
turned even when a command from the
host is processed correctly. See page
248.)