2-5
Section
Connection to a PC by the Host Link
41
[Making the PC system settings]
The possible settings and existing settings which can be set by the PC system
setting are as given below.
Item
Possible Setting
Existing Setting
Baud rate
1200/2400/4800/9600/19200 bps
9600/19200 bps
Stop bit
1 or 2 stop bits
2 stop bits
Parity
Even/odd/non-parity
Even parity
Data length
ASCII 7 bits
ASCII 7 bits
Unit #
00 to 31
Unit #00
S
C-series C200HS, C200HX/HG/HE, CPM1, CQM1
When connecting an NT620S/NT620C and a C200HS, C200HX/HG/HE,
CPM1, or CQM1 CPU unit, set the communication conditions in the PC system
setting area. Write the settings directly from the peripheral tool (e.g. SYSMAC
support tool) to the PC system setting area (data memory).
The switch settings made to enable “PC system setting” are described here.
For details on PC system setting area operations, refer to the manual for the
PC you are using (page 19).
[Switch settings] (C200HX/HG/HE, CQM1)
CPU unit DIP switch settings
RS-232C port communication condition settings
Set DIP switch 5 to OFF (right side) to enable
the PC system settings.
[Switch settings] (CPM1)
Set the mode setting switch to
the “HOST” (upper) position.
CPM1-
CIF01
CPM1
Summary of Contents for NT620C