![Omron NT620C Operation Manual Download Page 266](http://html1.mh-extra.com/html/omron/nt620c/nt620c_operation-manual_744559266.webp)
6-3
Section
Commands/Responses
255
Numeral memory table write command
(Sent from host to PT)
Command
Format
Data of 1 word
* *
* *
* *
* *
57
E
* *
m
t
1
t
2
t
3
t
4
W
N
(l
1
)
d1
m
,
dn
1
dn
m
d1
1
* *
2C
* *
* *
* *
* *
(l
2
)
(s
1
)
* *
(s
2
)
* *
[CR]
0D
Data of 1 word
1B
[ESC]
m
: Check sum present/absent (1 BCD digit)
0
: Absent
1
: Present
8
: Absent (only 1 table written)
9
: Present (only 1 table written)
t
1
to t
4
: First numeral memory table number written to
(4 BCD digits)
0000 to 0999
I
1
, I
2
: Number of written tables (2 BCD digits)
01 to 20 : 1 to 20 tables
When m is 8 or 9, omit this setting.
d1
1
to d1
m
, ..., dn
1
to dn
m
:
Contents of the numeral memory tables
(1 to 8 hexadecimal digits)
0 to FFFFFFFF
It is possible to omit initial zeroes so that there are less
than 8 digits.
Individual words of data are delimited by commas.
s
1
, s
2
: Check sum (2 hexadecimal digits)
When m is 0 or 8, omit this setting.
Response
Only if “Yes” is set for the “Response” memory switch, the response indicated
below is returned on normal completion.
Format
4E
30
30
32
30
1B
57
N
0
0
s
1
s
2
[ESC]
W
0D
[CR]
s
1
, s
2
: Check sum (2 hexadecimal digits)
This is always added (fixed as “20”).
Function
S
Writes the data of the specified number of numeral memory tables, starting
from the specified numeral memory table.
S
Writing from a maximum of 20 memory tables is possible at one time.
Summary of Contents for NT620C