2-5
Section
Connection to a PC by the Host Link
42
[PC system setting area settings]
Write settings to the PC system setting area (data memory) according to the port
used to connect to the NT620S/620C.
S
When using the RS-232C port of a C200HX/HG/HE
Channel #
Writing Value
Settings
DM6645
0001
Host link mode and conditions are set.
DM6646
0303
Data length: 7 bits, 2 stop bits, even parity,
baud rate: 9600 bps
DM6646
0304
Data length: 7 bits, 2 stop bits, even parity,
baud rate: 19200 bps
DM6648
0000
Unit # 0
S
When using port A of C200HX/HG/HE
Channel #
Writing Value
Settings
DM6555
0001
Host link mode
Set the conditions with the contents of DM.
DM6556
0303
Data length: 7 bits, 2 stop bits, even parity,
baud rate: 9600 bps
DM6558
0000
Unit No. 0
S
When using port B of C200HX/HG/HE
Channel #
Writing Value
Settings
DM6550
0001
Host link mode
Set the conditions with the contents of DM.
DM6551
0304
Data length: 7 bits, 2 stop bits, even parity,
baud rate: 19200 bps
DM6553
0000
Unit No. 0
S
When using CPM1
Channel #
Writing Value
Settings
DM6650
0001
Host link mode
Set the conditions with the contents of DM.
DM6651
0304
Data length: 7 bits, 2 stop bits, even parity,
baud rate: 19200 bps
DM6653
0000
Unit No. 0