8.3 Alarm/Warning Display and Troubleshooting
142
A.510
Overspeed
Occurred when the
power supply was
turned ON.
The SERVOPACK is faulty.
• Replace the SERVOPACK.
• Contact your Omron
Yaskawa representative.
Occurred when the
servomotor started
running or ran at
high speed.
The order of phases U, V,
and W of the servomotor
wiring is incorrect.
Correct the servomotor main
circuit cable wiring.
The encoder wiring is incor-
rect.
Correct the encoder wiring.
Malfunction occurred
because of noise interfer-
ence in the encoder line.
Take measures against noise
for the encoder line.
The input position refer-
ence was too large.
Reduce the reference value.
The SERVOPACK is faulty.
• Replace the SERVOPACK.
• Contact your Omron
Yaskawa representative.
A.710
Overload:
High load
Occurred when the
power supply was
turned ON.
The SERVOPACK is faulty.
• Replace the SERVOPACK.
• Contact your Omron
Yaskawa representative.
Occurred while the
servomotor was
running.
The effective torque
exceeds the rated torque, or
the starting torque largely
exceeds the rated torque.
Reconsider the load and oper-
ation conditions.
The SERVOPACK is faulty.
• Replace the SERVOPACK.
• Contact your Omron
Yaskawa representative.
(cont’d)
Alarm
Display
Alarm Name
Situation at Alarm
Occurrence
Cause
Corrective Actions