8.3 Alarm/Warning Display and Troubleshooting
148
A.E61
MECHA-
TROLINK-
II
Transmis-
sion Cycle
Error
Occurred when
MECHATROLINK-
II
communications
started or during
MECHATROLINK-
II
communications.
Communications with the
host controller disconnected
while the MECHATROLINK-
II
connection was estab-
lished with a CONNECT
command, and then com-
munications was started
again.
Turn the power supply OFF
and then ON again, or send a
DISCONNECT command to
release communications and
set up the communications
again.
The MECHATROLINK-
II
wiring is incorrect.
• Correct the MECHA-
TROLINK-
II
communica-
tions cable wiring.
• Connect terminators cor-
rectly.
MECHATROLINK-
II
data
receive error occurred
because of noise interfer-
ence.
Take measures against noise.
• Reconsider wirings for
MECHATROLINK-
II
commu-
nications cable and FG.
• Attach a ferrite core to the
MECHATROLINK-
II
commu-
nications cable.
The SERVOPACK is faulty.
• Replace the SERVOPACK.
• Contact your Omron
Yaskawa representative.
(cont’d)
Alarm
Display
Alarm Name
Situation at Alarm
Occurrence
Cause
Corrective Actions
TOEP_C710806_03A_1_0.book Seite 148 Montag, 2. Juli 2007 3:55 15