Executing Heating/Cooling Control
Section 4-4
4-4-2
Settings
To set heating/cooling control, set the “standard or heating/cooling,” “dead
band,” and “cooling coefficient” parameters.
Setting Heating/Cooling Control
Operating Procedure
Standard or heating/cooling = Heating/cooling
Setting the Cooling Coefficient
Operating Procedure
Cooling Coefficient = 10
Setting the Dead Band
Operating Procedure
Dead Band = 5
Initial Setting Level
1.
Press the
O
key for at least three seconds to move from the operation
level to the initial setting level.
2.
Select “heating/cooling control” in the initial setting level.
stnd
: Standard control
h-c
: Heating/cooling control
s-hc
stnd
Standard or
heating/cooling
Adjustment Level
1.
Select the “cooling coefficient” in the adjustment level.
2.
Use the
U
key to set the parameter to 10.00.
c-sc
1.00
Cooling
coefficient
c-sc
10.00
Adjustment Level
1.
Select the “dead band” parameter in the adjustment level.
2.
Use the
U
key to set the parameter to 5.0.
C
c-db
0.0
Dead band
C
c-db
5.0
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...