![background image](http://html.mh-extra.com/html/omron/e5az/e5az_user-manual_744338169.webp)
146
Advanced Function Setting Level
Section 5-7
• This parameter sets the function to be assigned to control output 1.
Note
(1) If
c-o
is assigned for standard control, a value equivalent to 0% is output.
(2) Can be selected for relay and voltage outputs only.
Related Parameters
Standard or heating/cooling: Page 123, Transfer output type: Page 127 (initial
setting level)
• This parameter sets the function to be assigned to alarm output 1.
Note
If
c-o
is assigned for standard control, a value equivalent to 0% will be
output.
out1
Control Output 1 Assignment
The transfer output type must be set
to OFF when the control output is a
current output.
Setting range
Default
none
: No function is assigned to control output 1.
o
o
:
Heating control output is output.
c-o
:
Cooling control output is output. (See note 1.)
alm1
: Alarm 1 is output. (See note 2.)
alm2
: Alarm 2 is output. (See note 2.)
alm3
: Alarm 3 is output. (See note 2.)
Function
Setting
See
See
alm1
Alarm
output 1 Assignment
Alarm output 1 must be assigned.
Setting range
Default
none
: No function is assigned to alarm output 1.
alm1
o
:
Heating control output is output.
c-o
:
Cooling control output is output. (See note. )
alm1
: Alarm 1 is output.
alm2
: Alarm 2 is output.
alm3
: Alarm 3 is output.
Function
Setting
■
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...