108
Adjustment Level
Section 5-4
This parameter executes auto-tuning (AT).
• The MV is forcibly increased and decreased around the set point to find
the characteristics of the control object. From the results, the PID con-
stants are automatically set in the “proportional band” (P), “integral time”
(I), and “derivative time” (D) parameters.
• This parameter is normally
off
. If you press the
U
key, the parameter is
turned ON and AT is executed. AT cannot be executed when control is
stopped or during ON/OFF control.
• When AT execution ends, the parameter setting automatically returns to
off
.
Related Parameters
Proportional band, Integral time, Derivative time (adjustment level): Page 113
PID ON/OFF (initial setting level): Page 122
This parameter enables/disables writing of parameters to the E5CZ from the
host (personal computer) using communications.
ON:
Writing enabled
OFF: Writing disabled
• Default: OFF
Related Parameters
MB command logic switching (advanced function setting level): Page 141
Communications Unit No., Communications baud rate, Communications data
length, Communications parity, Communications stop bits (communications
setting level): Page 149
at
AT Execute/Cancel
The E5CZ must be in operation, and
control must be 2-PID control.
Function
Operation
See
See
cmwt
Communications Writing
Communications must be supported.
Function
Setting
See
See
■
■
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...