Advanced Function Setting Level
Section 5-7
• This parameter sets the time constant for the input digital filter. The fol-
lowing diagram shows the effect on data after passing through the digital
filter:
This parameter adds a display at the beginning of the operation level for the
process value (PV). If there is no need to display the set point, use this to dis-
play only the present temperature.
Set to ON to display, and OFF to not display.
This parameter is used to display the manipulated variable (MV).
The manipulated variable is displayed when the “MV monitor (heating) and
(cooling)” parameters are set to ON, and not displayed when these parame-
ters are set to OFF.
Related Parameters
MV monitor (heating): Page 104, MV monitor (cooling): Page 105 (operation
level)
inf
Input Digital Filter
Setting range
Unit
Default
0.0 to 999.9
Second
0.0
Function
0.63 A
A
PV before passing through filter
PV after passing through filter
(Time
constant)
Input digital filter
Time
Setting
pvad
Additional PV Display
Setting range
Default
on
: Displayed,
off
: Not displayed
off
Function
Setting
o-dp
MV Display
Setting range
Default
on
: Displayed,
off
: Not displayed
off
Function
Setting
See
See
■
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...