Using Event Inputs
Section 4-5
Number of Multi-SP Uses = 1
Number of Multi-SP Uses = 2
Note
Event inputs can be used on the
following Controllers. E5CZ-
@
2M
@@
with
E53-CZB or E53-CZHB
,
E5AZ-
@
3
@
M
@@
with E53-AZB
,
E5EZ-
@
3
@
M
@@
with E53-AZB
.
Turn the event inputs ON or OFF while the E5AZ is turned ON.
Event input ON/OFF changes are detected for inputs of 50 ms or longer.
Using Key Operations
You can select any of the set points 0 to 3 by changing the set value of the
“multi-SP uses” parameter. The “multi-SP uses” display conditions are as fol-
lows:
• If the Controller does not support event inputs, the “multi-SP uses”
parameter must be set to ON.
• If the Controller supports event inputs, the “number of multi-SP uses”
parameter must be set to 0 and the “multi-SP uses” parameter must be
set to ON.
The following table shows the relationship between the “multi-SP uses”
parameter set value and the selected set point.
Note
The set point can also be switched using communications.
Event input 1
Selected set point
OFF
Set point 0
ON
Set point 1
Event input 1
Event input 2
Selected set point
OFF
OFF
Set point 0
ON
OFF
Set point 1
OFF
ON
Set point 2
ON
ON
Set point 3
Multi-SP
Selected set point
0
Set point 0
1
Set point 1
2
Set point 2
3
Set point 3
■
■
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...