111
Adjustment Level
Section 5-4
These parameters set the set points when the multi-SP function is used.
The values set in these parameters can be selected by operating the keys on
the front panel or by using event inputs.
• When the set point has been changed, the set value of the set point (0 to
3) selected by the multi-SP inputs is also changed to the same value.
• The decimal point position depends on the selected sensor. During ana-
log input, it depends on the “decimal point” parameter setting.
Related Parameters
Process value/set point (operation level): Page 99
Input type (initial setting level): Page 119
Number of multi-SP uses: Page 131, Event input assignment
1 and Event
input assignment
2, Multi-SP uses: Page 132 (advanced function setting
level)
Sometimes an error occurs between the set point and the actual temperature.
To offset this, a compensated value can be obtained by adding an input shift
value to the input. The compensated value is displayed as the measurement
value and used for control.
The entire input range is shifted by a fixed rate (1-point shift). If the input shift
value is set to
−
1
°
C, control will be performed for a value 1
°
C lower than the
measured temperature.
Related Parameters
Input type (initial setting level): Page 119
Input shift type (advanced function setting level): Page 142
sp-0
SP 0
The “number of multi-SP uses”
parameter must be set to 1 or 2.
The “multi-SP uses” parameter must
be set to ON.
sp-1
SP 1
sp-2
SP 2
sp-3
SP 3
Setting range
Unit
Default
SP lower limit to SP upper limit
EU
0
Function
Setting
See
See
ins
Temperature Input Shift
The “input type” parameter must be
set for a thermocouple or resistance
thermometer, and the “input shift
type” parameter must be set to a
one-point shift.
Setting range
Unit
Default
−
199.9 to 999.9
°
C or
°
F
0.0
Function
Setting
See
See
■
■
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...