Initial Setting Level
Section 5-6
5-6
Initial Setting Level
This level is used to set up the basic Temperature Controller specifications. In
this level, you can set the “input type” parameter to set the sensor input to be
connected, limit the setting range of set points, set the alarm modes, and per-
form other operations.
To move from the operation level to the initial setting level, press the
O
key
for at least 3 seconds with any parameter displayed except for the “auto/man-
ual switch” parameter.
• The initial setting level is not displayed when the “initial/communications
protect” parameter is set to 2. It can be used when the “initial/communica-
tions protect” parameter is set to 0 or 1.
• If the “input type” parameter is set for an analog input, the following
parameters will be set: Scaling upper limit, Scaling lower limit, and Deci-
mal point.
Operation
Level
Initial Setting
Level
Control stops.
Power ON
Control in progress
Control stopped
25
100
C
Press the
O
Key
for at least 1 s.
Press the
O
Key
for at
least 1 s;
display
will flash.
Press the
O
Key for at
least 3 s.
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...