90
Using the Transfer Output
Section 4-13
Operating Procedure
The following procedure sets the transfer output for an SP range of
−
50 to
200.
Operation Level
Initial Setting Level
1.
Press the
O
key for at least 3
seconds to move from the operation level
to the initial setting level.
Initial Setting Level
2.
Select the “transfer output type” parameter by pressing the
M
key.
3.
Press the
U
key to select
sp
(set point).
Initial Setting Level
4.
Select the “transfer output upper limit” parameter by pressing the
M
key.
5.
Use the
D
key to set the parameter to 200. The default is 1300.
Initial Setting Level
6.
Select the “transfer output lower limit” parameter by pressing the
M
key.
7.
Use the
U
key to set the parameter to
−
50. The default is
−
200.
Operation Level
8.
To return to the operation level, press the
O
key for at least 1 second.
C
25
100
PV/SP
in-t
5
Input type
tr-t
off
Transfer output
type
tr-t
sp
C
tr-h
1300
Transfer output
upper limit
C
tr-h
200
C
tr-l
-200
Transfer output
lower limit
C
tr-l
-50
C
25
100
PV/SP
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...