61
Shifting Input Values
Section 4-1
Figure 1 Offset Configuration for an Infrared Temperature Sensor
Method for a 1-point Shift
1,2,3...
1.
In the configuration shown in
Figure 1
, bring the set point to near the value
at which the temperature of the control target is to be controlled. Assume
that the control target temperature (C) and the thermocouple temperature
(B) are the same.
2.
Check the control target temperature (B) and the Controller readout (A).
Subtract the Controller readout temperature (A) from the control target
temperature (B), and set
insl
and
insh
to the result as the input shift val-
ue. The shift is illustrated in
Figure 2
.
3.
After setting the input shift values, check the Controller readout (A) and the
control target temperature (B). If they are almost the same, this completes
shifting the temperature input.
Figure 2 Illustration of 1-Point Shift
Infrared Temperature
Sensor
(C) Control target
(B) Thermometer
(A) E5CZ/AZ/EZ Temperature Controller
Output
Power supply
C
insh
10.0
C
insl
10.0
Upper-limit
temperature
input shift
value
Lower-limit
temperature
input shift
value
0
Controller readout (A)
Controller readout after
shifting (e.g., 120
°
C)
Controller readout before
shifting (e.g., 110
°
C)
Before shifting
After shifting
Input shift value (e.g., 10
°
C)
Near set point
(e.g., 120
°
C)
Control target temperature (B)
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...