![Omron E5AZ User Manual Download Page 101](http://html.mh-extra.com/html/omron/e5az/e5az_user-manual_744338101.webp)
78
Using the Key Protect Level
Section 4-9
Operation/Adjustment
Protect
The following table shows the relationship between set values and the range
of protection.
• Parameters are not protected when the set value is set to 0.
• The default is 0.
Initial Setting/
Communications
Protect
This protect level restricts movement to the initial setting level, communica-
tions setting level, and advanced function setting level.
• The default is 1.
Setting Change
Protect
This protect level restricts key operations.
• The default is OFF.
• The all protect indication (
) will light when setting change protect is
set.
oapt
0
Level
Set value
0
1
2
3
Operation
level
PV
Can be dis-
played
Can be dis-
played
Can be dis-
played
Can be dis-
played
PV/SP
Can be dis-
played and
changed
Can be dis-
played and
changed
Can be dis-
played and
changed
Can be dis-
played
Others
Can be dis-
played and
changed
Can be dis-
played and
changed
Cannot be
displayed and
moving to
other levels is
not possible
Cannot be
displayed and
moving to
other levels is
not possible
Adjustment level
Can be dis-
played and
changed
Cannot be
displayed and
moving to
other levels is
not possible
Cannot be
displayed and
moving to
other levels is
not possible
Cannot be
displayed and
moving to
other levels is
not possible
icpt
1
Set
value
Initial setting level
Communications
setting level
Advanced function
setting level
0
Movement possible
Movement possible
Movement possible
1
Movement possible
Movement possible
Movement not possible
2
Movement not possible
Movement not possible
Movement not possible
wtpt
off
Set value
Description
OFF
Settings can be changed using key operations.
ON
Settings cannot be changed using key operations. (The protect level
settings, however, can be changed.)
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...